CITY OF LODI COUNCIL COMMUNICATION
01
AGENDA TITLE: Specifications and Advertisement for Bids for
Underground Primary Electrical Cable
MEETING DATE: June 7, 1995
SUBMITTED BY: Electric Utility Director
RECOMMENDED ACTION: That the City Council approve the specifications and
authorize advertisement for bids for 30,000 feet of
#2AWG, and 22,500 feet of 750Kcmil underground
primary conductor for the Electric Utility Department.
BACKGROUND INFORMATION: This cable will be needed for installation in new residential
and commercial subdivisions scheduled during the next
twelve months, and to provide an inventory for routine or
emergency maintenance of the existing electrical system.
Some of the developments where this cable is required are Sunwest Plaza, Johnson Ranch, Century
Meadows, Towne Ranch, Lodi West, J C Penney, and the Lodi Avenue Lucky Store projects.
FUNDING:
BID OPENING:
Prepared by Joel Harris, Purchasing Officer
The estimated cost of this purchase is $95,000, and fund-
ing is available in the Electric Utility Department's Oper-
ating Fund.
June 28, 1995
)OVA
Hans Hansen, Acting Director, Electric Utility Department
APPROVED:
THOMAS A. PETERSON
City Manager
cc -1
15 -KV XLPE INSULATED JACKETED AND NON-JACKETED CONCENTRIC NEUTRAL CABLE
1.0 GENERAL
Cable furnished under these specifications shall be limited to cross -lined thermosetting
polyethylene (XLPE) insulated concentric neutral cable rated 15,000 volts and suitable for
installation in ducts or for direct burial in earth, in wet or dry locations, with normal conductor
temperatures up to 90°C. Cables furnished shall meet the requirements of the applicable NEMA,
ICEA, AEIC and ASTM Standards, latest edition thereof, unless otherwise noted in this
Specification.
2.0 CABLE
A. Conductor
Insulated conductor shall be aluminum alloy, EC Grade, Class B, stranded or compressed
strand, three-quarter or half hard.
B. Conductor Shield
The conductor (strand) shielding shall be extruded and shall consist of virgin black semi-
conducting cross-linked, thermosetting polyethylene. The extruded shield shall have an
average thickness of not less than 15 mils when measured over the top of the strands and a
minimum thickness of not less than 12 mils. The outer surface of the conductor shield shall
be cylindrical and shall be firmly bonded to the overlaying insulation.
C. Insulation
Insulation shall be unfilled, semi -transparent, cross-linked thermosetting polyethylene
extruded directly over the conductor shield. The average insulation thickness shall not be
less than 220 mils and the minimum thickness shall not be less than 90% of this value.
D. Insulation Shield
The insulation shielding shall be extruded and shall consist of one layer of virgin black semi-
conducting, cross- linked thermosetting polyethylene, compatible with and extruded over the
hmser\adminlspecslcable Page I
insulation. It shall maintain its shielding properties after expos,., a to normal operating
temperatures and environs. The insulation shield compound and thickness shall be in
accordance with AEIC Standard.
Conductor shield, insulation and insulation shield shall be installed on the conductor using the
triple extruding, dry cure method.
F. Concentric Neutral
The concentric conductor shall be composed of a number of round annealed bare (uncoated)
copper wires helically wrapped around the cable. The number and size of the neutral wires
shall be as specified in Table I. The length of lay shall not be less than 6 nor more than 10
times the diameter over the concentric wires.
G. Overall Jacket (if required on Proposal Form
An extruded, encapsulating and insulating layer of linear, low density black polyethylene,
(Union Carbide DFDB 6425, British Petroleum BP D 995, or approved equivalent) shall be
applied over the concentric neutral wires in accordance with ICER S-66-524, Part 4.3, except
where modified by this Specification. The minimum thicknesses of this encapsulating jacket
over the concentric wires shall be as follows:
Conductor Size (AWG or KCM) Minimum Thickness (Mils)
#2 50
#2/0 80
750 & 1,000 110
H. Testing and Guarantee
Testing of cable shall be performed according to procedures set forth by the ICEA, AEIC and
ASTM Standards. Certified copies of pass/fail test results shall be supplied. Any cable found
defective either upon inspection, testing or installation will be returned at the manufacturer's
expense.
h:userWminlspecslcable Page 2
Any conditional bids such as "subject to availability in stock" will be rejected. Cable shall be
furnished according to Table I below:
Conductor Size
Conc. Neutral
NEMA
AWG or KCM
Size - AWG
Material
Insulation
Reel Code
(No. of Strands)
(Min. No. of Wires)
Phase (Neut.)
Thick. (Mils)
Number
#2 (7)
#14 (10)
Alum. (Cu)
220
5832
#2/0 (19)
#14 (9)/#12 (6)
Alum. (Cu)
220
5832
750 (61)
#12 (24)/#10 (15)
Alum. (Cu)
220
7848
1,000 (61)
#10 (20)
Alum. (Cu)
220
7848
NOTE: Refer to proposal forms for specific sizes, quantities and jacketing requirements.
J. Reels
1. Makeup and Length:
Reels are to be shipped full to their maximum capacities.
Each cable reel shall have adequate protective covering across the flanges. Such
covering to consist of wood members from flange to flange covering the entire
circumference of the reel (lagging). The lagging shall be nailed to the flange perimeters
and shall be further secured with at least two steel bands around the reel. Each end of
the cable shall be firmly secured to the reel.
EXCEPTION: Reels containing #2 or #210 AWG conductor shall be paper wrapped only, no
lagging.
h:userladminlspecslcable Page 3
RM I F MM
Each reel shall be marked with a durable label securely attached to a flange of the reel
and plainly marked stating the destination, the purchaser's order number, shipping length
of cable on reel, weight of reel (tare weight), total weight of cable on reel, type and size of
conductor, insulation type and thickness, voltage rating and manufacturer's identification
number.
Cable ends shall be adequately sealed with a water seal -type material and plastic end caps
secured by tape to prevent penetration of moisture. There shall be no water in the stranded
conductor of the cable when the reel is shipped. Reels shall be shipped upright. All
shipments shall be prepaid, F.O.B. Lodi, California.
h:user\admin\specs\cable Page 4