HomeMy WebLinkAboutAgenda Report - February 1, 2023 C-05CITY OF L *•% f o CALIFORNIA AGENDA ITEM C46'5 COUNCIL COMMUNICATION AGENDA TITLE: Adopt Resolution Authorizing City Manager to Execute Change Order No. 1 with Schweitzer Engineering Laboratories Engineering Services, Inc. ($421,578) for Substation Relay Modernization Capital Improvement Project and Appropriating Funds ($422,000) MEETING DATE: February 1, 2023 PREPARED BY: Electric Utility Director RECOMMENDED ACTION: Adopt a resolution authorizing the City Manager to Execute Change Order No. 1 with Schweitzer Engineering Laboratories Engineering Services, Inc. (SEL) in the amount of $421,578 for the Substation Relay Modernization Capital Improvement Project and appropriating funds in the amount of $422,000. BACKGROUND INFORMATION: Lodi Electric Utility (LEU) is requesting an additional $422,000 for the Substation Relay Modernization Project due to increased contractor installation and commissioning support as well as the addition of one new relay protection panel. LEU's requirement for Industrial Substation as part of this project is to ensure all equipment pertaining to a specific relay protection panel is de -energized for contractor and equipment safety. Due to this requirement, the time -per -panel increases from four to twelve weeks for installation and commissioning support. In addition, the purchase of a new spare substation power transformer, approved by City Council on January 18, 2023, will require a new relay protection panel to be constructed where a blank panel currently resides within Industrial Substation. SEL, LEU's substation relay contractor, will provide and install all components of the specific substation power transformer as well as the related drawings and diagrams, FISCAL IMPACT: The proposed Change Order No. 1 totals $421,578. FUNDING AVAILABLE: Staff are requesting an appropriation of funds in the amount of $422,000 to 50199000.77020 (EU CP -22005. Contracts) for a total approved Fiscal Year 2023 project budget of $1,766,073. Andrew Keys Andrew Keys Deputy City Manager/Internal Services Director A�'�- Jeff Berkheimer Electric Utility Director APPROVED:OVY ROwSc. auF!r ,wn 14 2013 i1:SaPST) Stephen Schwabauer, City Manager 4k CITY OF LODI PROPOSED CHANGE ORDER PROJECT: Substation Relay Modernization Project CO No.: 1 CONTRACTOR: PCO No.: SEL Engineering Services, Inc. RFI No.: ARCHITECT/ENGINEER: FI No.: City of Lodi Submit Proposal Within 15 Days Upon Receipt of This Request Brief Description Of Work Change Order #1: Additional installation and commissioning support and relay protection panel for Industrial Substation Relay Upgrade Project per attached proposal dated January 17, 2023. Request, Proposal, Recommendation And Approval Requesting Official: Jasminder Singh Request Date: 2/1/2023 Schedule Impact: See Below Days Contractor Proposal Date: 1/17/2023 Add Amount: $421,578.00 Deduct Amount $0.00 Reason For Change: Additional installation and commissioning support and relay Account: EUCP-22005. Contracts protection panel for Industrial Substation Relay Upgrade Project CONTRACTOR AGREES TO FURNISH ALL LABOR AND MATERIALS AND PERFORM ALL WORK REQUIRED TO COMPLETE THE ABOVE DESCRIBED WORK CHANGE IN ACCORDANCE WITH THE REQUIREMENTS FOR SIMILAR WORK COVERED BY THE CONTRACT EXCEPT AS OTHERWISE STIPULATED HEREIN FOR THE STATED CONSIDERATION. TO PERFORM THE CHANGES FOR THE AMOUNT INDICATED WHICH INCLUDES ANY EXTENDED OR JOBSITE OVERHEAD, DISRUPTION, RIPPLE EFFECT AND OTHER IMPACT COSTS. NO WORK WILL BE STARTED UNTIL THIS PROPOSAL IS ACCEPTED. IF THE CONTRACTOR DOES NOT SIGN ACCEPTANCE OF THIS ORDER, THE CONTRACTOR SHOULD REFER TO SECTION 4- 1.03A OF THE STANDARD SPECIFICATIONS REGARDING FILING A WRITTEN PROTEST WITHIN THE SPECIFIED TIME. ORIGINAL CONTRACT: $1,024,073.00 PREVIOUS ADDS: $0.00 SEL Engineering Services, Inc. Date PREVIOUS DEDUCTS: $0.00 THIS CHANGE ORDER: $421,578.00 Jeff Berkheimer, Electric Date Utility Director TOTAL CONTRACT AMOUNT $1,445,651.00 INCLUDING ALL CHANGE ORDERS: Stephen Schwabauer, Date City Manager ORIGINAL COMPLETION DATE: 3/28/2023 ADJUSTED CONTRACT 7/3/2023 COMPLETION DATE: SEL CCO 1 1/19/2023 SELSCHWEITZER SEL Engineering Services, Inc. ENGINEERING 810 Vaca Valley Parkway, Suite 110 • Vacaville, CA 95688 USA LABORATORIES Phone: +1.509.332.1890 • Fax: +1.707.452.1050 www.selinc.ccm • esinfo@selinc.com Project Change Order Description Lodi Electric This Change Order summarizes various changes for the design, installation, and commissioning services of this project. Customer Utility Department Contract/PO Number LPM9272674 Customer Contact Name Jasminder Singh Change Order Number 01 Parts Removed: Industrial • Qty 8: SEL -735 Power Quality and Revenue Meter SEL ES Project Name Substation Relay Change Order Date 01/17/2023 • Axion Cabinet Upgrade - 60kV Parts Added: SEL ES Project Number 022962.000.00 Date Response Required 01/31/2023 SEL ES Project Manager Mandeep Panech SEL ES Contact Name Mandeep Panech Description Basis of Change: This Change Order summarizes various changes for the design, installation, and commissioning services of this project. Description Cost Item 1: Removal of Survalent HMI option: SEL ES Project 022962.002.00 ($103,800.00) This was quoted in the original proposal as Option 3. Item 2: Change in Part Numbers: SEL ES Project 022962.003.00 ($59,228.00) Parts Removed: • Qty 8: SEL -735 Power Quality and Revenue Meter • Qty 4: SEL -487B Buss Differential and Breaker Failure Relay • Qty 2: SEL -451 Protection, Automation, and Bay Control System • Axion Cabinet Parts Added: • Qty 4: SEL -587Z High -Impedance Differential Relay • Qty 2: SEL -487E Transformer Protection Relay • Loose parts like fuses, terminal blocks, blank plates, bezels. Item 3: Design Changes: SEL ES 022962.000.00 $70,750.00 • Single line diagram for the project had multiple updates. The main reason for this was change of protection relays for breakers and protection relays for bus. • Panel layouts and plate fabrication drawings had multiple updates. The main reason for this was change of protection relays for breakers and protection relays for bus and SCADA panel layout design Confidentiality Notice: The information contained in this query is privileged and confidential information and is intended solely for the use of the individual or entity to whom it is addressed. If you are not the intended recipient or the person responsible for delivering the material to the intended recipient, you are hereby notified that any dissemination, disclosure, copying, or distribution of this communication is strictly prohibited. If you received this communication in error, please notify us immediately by telephone and destroy this material accordingly. © 2022 by SEL ES (All rights reserved.) Page 1 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 • Existing AC/DC schematics were updated to reflect terminal block information for the CT, PT, and breaker control connections that will help during phase upgrades and will make schematics more informational. Additional drawings were created to depict circuit wiring between locations. • Additional scope for the cable schedule. The cable schedule will now include cable name, cable conductor count, to and from location, and terminals each conductor will land on in each location. Detail will be added for cables in the protection panels. For example: Protection panel to protection panel, protection panel to field equipment, and protection panel to DC board. • Field wire diagrams will be updated to show new cables and wire modifications which are done as part of this upgrade. • Panel I IA was updated with new equipment that required updated existing or creating new PL, NP, AC, DC, and WD updates. Item 4: Protection Settings for power failure scheme: SEL ES 022962.000.00 $11,875.00 • Programming of two (2) SEL -751 relays for PG&E lines power failure schemes. • Updates to FDS to include the change to power failure scheme. • Update test plan to include power failure scheme testing. Item 5: Isolation, commissioning, testing, and Restoration (ICTR) Plan development: $63,625.00 SEL ES 022962.000.00 • Original proposal was priced to complete commissioning activities during complete shutdown. During project execution it was determined that the City of Lodi can only take outages per line. Regarding bus relay upgrade outage can be taken on only one (1) bus. In total, the team finalized on twelve phases for commissioning. • See details of phases outlined in Item 7, test plan will be written to account for phase work that is being done and drawings will be edited to reflect phase work conditions. • SEL ES will work with project team from Lodi, EPS and other contractors involved to account for activities and work that is being performed during phase outage to minimize the impact on rest of the system. Note: Review of ICTR will be the responsibility of all responsible personnel involved in the project, SEL ES will be taking the lead in preparation of the ICTR. Item 6: Commissioning Removed from the Scope of Work: SEL ES 022962.000.00 ($184,799.00) Items listed below are from the original proposal. Items 5 and 7 of this change order include the additional work required as per revised commissioning phases. • Mobilize two (2) field services technicians to the customer site to complete the installation of all equipment provided with this proposal. Work will be completed in two (2) mobilizations of two (2) weeks each. • Mobilize protection and automation engineers based out of the SEL ES Vacaville, CA office to the customer site in Lodi, CA to provide onsite installation and commissioning support during the field service technician mobilizations. • Develop commissioning plans for the retrofit upgrade. • Develop commissioning plans for the Automation commissioning. Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 2 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Item 7: Commissioning Added to the Scope of Work: SEL ES 022962.000.00 I $572,500.00 Mobilize two (2) field service technicians to the customer site to complete installation of all SEL supplied equipment. Work will be completed over twelve mobilizations of four (4) days each for a total of 120 weekdays Mobilize protection and automation engineers to provide onsite installation and commissioning support during field service mobilizations and energization. SEL ES has planned for a total of 96 weekdays Phase # Task CB ME Scope of Work 1 Panel 7A - RTAC Upgrade Install RTAC Plate, this plate will also have bus diff for Bus 1. Run Communication cables to each panel for new relaying Panel 1 - Henning Line Upgrade 6060 and 6061 Demolition of Existing 2 relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 3 Panel 3 - Killelea Line Upgrade 6065 Demolition of Existing relaying install new plate City planning to run new CT wiring from breaker to control house Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 3 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 4 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 4 Panel 2 - Xfinr T1 Line 6062 and 6063 Demolition of Existing Upgrade relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 4 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 5 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com 5 Panel 5 — Mclane Line Upgrade 6089 and 6069 Demolition of Existing relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 6 Panel 6 — Xfinr T3 Line 6070 and 6071 Demolition of Existing Upgrade relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing Energization Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 5 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 6 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 7 Panel 9 — PG&E LODI- 52 Demolition of Existing Industrial relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing PG&E PPI Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 8 Panel 10 —PG&E Industrial 32 and 42 Demolition of Existing Tap Line relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT Phasing Relay testing Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 6 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 7 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com Relay and breaker functionality testing SCADA testing PG&E PPI Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 9 Panel 11 — PG&E Lockeford 12 and 22 Demolition of Existing Industrial Line relaying install new plate City planning to run new CT wiring from breaker to control house Shorten the CTs previously used for BF relay and run to respective Bus differential cabinet. Run RTU wiring related to breakers to AXION Secondary current injection from the breakers to verify CT phasing Relay testing Relay and breaker functionality testing SCADA testing PG&E PPI Energization Note: DO NOT perform breaker failure functional testing, it can trip the bus lockout 10 Panel I IA - Power Install new SEL -751 relay Plate and Test Switch Existing 94 devices are maintained 11 Panel 7B — Bus 1 Differential 6061, 6063, Verify Bus 1 is out of 6065, 6069, service 6071, 52, 42, and 22 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 7 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 8 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com Terminate the BUS 1 BF CTs to both SEL -587Z Secondary current injection from the breakers to verify CT phasing and summation Relay Testing 86-B1 trip and block close testing Energization load each breaker 12 Panel 8 — Bus2 Differential 6060, 6062, Verify Bus 2 is out of 6068, 6070, service Demolition of 32, and 12 Existing relaying install new plate Terminate the BUS2 BF CTs to both SEL -587Z Secondary current injection from the breakers to verify CT phasing and summation Relay Testing 86-132 trip and block close testing Energization load each breaker 13 Demolition of RTU Cabinet Demolish RTU Cabinet Item 8: Additional plate design and fabrication: SEL ES 022962.003.00 $50,655.00 • Fabricate plate with the following BOM: o SEL -487E with MOT: 0487E3X41 IXXBOX4377474X o SEL -9510 control switch module o Qty 4: 1OPole, 6CT, 4P Test switches o Qty 5: 1OPole, 10P Test switches o Qty 2: 1OPole, 8CT, 2P Test switches o Qty 1: Lockout relay • The following deliverables will be included for plate only: o Panel Layout o Wiring diagrams for plate o Name plate o Schematics Total $421,578.00 Equipment Deliverables • All deliverables from the original proposal apply to this Change Order • Additional plate as per Item 8 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 8 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Documentation Deliverables • All deliverables from the original proposal apply to this Change Order • Document deliverables for Item 4, Item 5, and Item 8 Deliverables to SEL ES • All deliverables from the original proposal apply to this Change Order Clarifications • All clarifications and exceptions from the base project apply to this change order. • The updated pricing from EPS is not reflected in this Change Order. We have not received pricing from EPS as of the date of processing this Change Order. • We have estimated taxes for the equipment in Item 8, they will be billed at the statutory rates applicable at time of invoicing. Cost Impact ($103,800.00) Item 1: Survalent HMI ($59,228.00) Item 2: Material Change $70,750.00 Item 3: Design Changes $11,875.00 Item 4: Relay programming $63,625.00 Item 5: Create ICTR Plans ($184,799.00) Item 6: Deduct for commissioning $572,500.00 Item 7: Installation and Commissioning for twelve phases $50,655.00 Item 8: Additional Plate (Material and Design, includes estimated tax of $3,807.00) US $421,578.00 TOTAL Payment Milestone Schedule • On approval of this change order $50,000.00 • Completion of design $55,000.00 • ICTR Plan development complete $55,000.00 • Complete Relay settings $50,000.00 • Commissioning Phases 1 thru 4 $60,000.00 • Commissioning Phases 5 thru 9 $60,000.00 • Commissioning Phases 10 thru 12 $46,323.00 • Shipment of Panel $45,255.00 Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 9 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com SEL ES Project Number: 022962.000.00 Schedule Impact • The schedule will be impacted for both equipment delivery, installation, and commissioning Change Order Summary $991,090.00 Original Contract/PO $421,578.00 Amount from this Change Order # 01 US $1,412,668.00 TOTAL Validity This quotation is valid for 60 days. SEL ES reserves the right to withdraw this offer if mutually accepted credit terms cannot be agreed upon. Authorization Customer/vendor agrees to revise the Contract/PO to reflect the changes described in this Change Order. Signature Date Name Title Rev.20220208 © 2022 by SEL ES (All rights reserved) Page 10 of 10 SEL ES PROPRIETARY INFORMATION www.selinc.com Capital Improvement Plan FY 2022-2023 Project Title: Substation Relay Modernization Munis Project Code: EUCP-22005 #196 Section I: Description District Nos: 2,3,4,5 Project Length 7/22-6/25 Priority High The purpose of the multi-year project is to upgrade and modernize three of the four total substations with modern protection devices to replace outdated and end -of -life equipment. The modernization will allow for greater protection and visibility of highly valuable substation equipment as well as the coordination of protection and power supply between Pacific Gas and Electric and Lodi Electric Utility. Justification/factor driving project Per Pacific Gas and Electric (PG&E), our incoming relay protection within Industrial Substation has significant cordination (device -to -device safety) issues that results in slower clearing times and reduced reiability for all of Lodi Electric Utility's (LEU) power supply. In addition to our incoming power supply protection is the outdated equipment we have at Industrial Substation, Henning Substation, and Killelea Substation. To solve this, substation modernization and standardization would upgrade and standardize all remaining protection and control devices, remote terminal units, and accompanied SCADA screens. Modernizing and standardizing our substation equipment will not only increase asset reliability and protection, but will also allow for greater field worker safety due to the increased protection capabilities built -into the equipment, proven at McLane Substation. The standardization process will eliminate the need to stock multiple vendor equipment types, while also increasing LEU Technician understanding and familiarity of single -vendor equipment throughout all substations. Additional Information FY 22 and 23 includes funding in the amount of $1,024,073 + $120K for Industrial (60 W). Funds are being moved from FY 25 to FY 23 for Killelea (60 kV and 12 kV) and reduced based on identified cost savings by performing work using existing utility staff ($200K). FY 24 includes funding for Industrial (12 kV) and also includes an updated estimate and identified cost savings ($200K). FY 25 includes funding for Henning (60 kV and 12 kV) and also includes an updated estimate and identified cost savings ($200K). FY 23 includes additional monies added in February 2023 for increased contractor installation and commissioning support as well as the addition of one new relay protection panel ($422K). Section II: Estimated Project Costs Expenditure Prior Years FY 21/22 FY 22123 Budget FY 23/24 FY 24125 FY 25126 FY 26/27 Future Yrs Total Estimate Internal Staff $ $ $ 1,024,073 $ 120,000 $ 398,000 $ 1,546,073 $ 80,000 $ 222,000 $ 158,000 $ 120,000 Contracts $ 522,000 $ - Miscellaneous $ $ $ $ 62,000 $ 80,000 $ - $ - Total Capital Costs $ 200,000 $ - $ - $ - $ 2,166,073 $ - $ 11024,073 $ 742,000 $ 200,000 Section III: Funding Sources/Methods o Funding Source(s) Prior Years FY 21/22 FY 22123 Budget FY 23124 FY 24125 FY 25126 FY 26127 Future Yrs Total Estimate 501 - EU Outlay Capital Reserve Fund $ $ 1,024,073 $ 742,000 $ 200,000 $ 200,000 $ 2,166,073 $ $ - Total Project Financing $ - $ 1,024,073 $ 742,000 $ 200,000 $ 200,000 $ - $ - $ - $ 2,166,073 RESOLUTION NO. 2023-22 A RESOLUTION OF THE LODI CITY COUNCIL AUTHORIZING THE CITY MANAGER TO EXECUTE CHANGE ORDER NO. 1 WITH SCHWEITZER ENGINEERING LABORATORIES ENGINEERING SERVICES, INC., OF VACAVILLE, FOR SUBSTATION RELAY MODERNIZATION CAPITAL IMPROVEMENT PROJECT; AND FURTHER APPROPRIATING FUNDS WHEREAS, Lodi Electric Utility (LEU) is requesting additional funding for the Substation Relay Modernization Project due to increased contractor installation and commissioning support, as well as the addition of one new relay protection panel; and WHEREAS, LEU's requirement for Industrial Substation as part of this project is to ensure all equipment pertaining to a specific relay protection panel is de -energized for contractor and equipment safety; and due to this requirement, the time -per -panel increases from four to twelve weeks for installation and commissioning support; and WHEREAS, in addition, the purchase of a new spare substation power transformer, approved by City Council on January 18, 2023, will require a new relay protection panel to be constructed where a blank panel currently resides within Industrial Substation; and WHEREAS, Schweitzer Engineering Laboratories Engineering Services, Inc., LEU's substation relay contractor, will provide and install all components of the specific substation power transformer, as well as the related drawings and diagrams; and WHEREAS, staff recommends the appropriation of funds in the amount of $422,000 to Account No. 50199000.77020 for said project (EUCP-22005). NOW, THEREFORE, BE IT RESOLVED that the Lodi City Council does hereby authorize the City Manager to execute Change Order No. 1 with Schweitzer Engineering Laboratories Engineering Services, Inc., of Vacaville, California, in the amount of $421,578 for the Substation Relay Modernization Capital Improvement Project; and BE IT FURTHER RESOLVED that the Lodi City Council does hereby authorize the appropriation of funds to the Substation Relay Modernization Capital Improvement Project (EUCP-22005) for Fiscal Year 2023 in the amount of $422,000, as noted above, for a total approved budget of $1,766,073; and BE IT FURTHER RESOLVED, pursuant to Section 6.3q of the City Council Protocol Manual (adopted 11/6/19, Resolution No. 2019-223), the City Attorney is hereby authorized to make minor revisions to the above -referenced document(s) that do not alter the compensation or term, and to make clerical corrections as necessary. Dated: February 1, 2023 ------------------------------------------------------------------------ ------------------------------------------------------------------------ I hereby certify that Resolution No. 2023-22 was passed and adopted by the City Council of the City of Lodi in a regular meeting held on February 1, 2023 by the following vote: AYES: COUNCIL MEMBERS — Bregman, Khan, Nakanishi, and Mayor Hothi NOES: COUNCIL MEMBERS — None ABSENT: COUNCIL MEMBERS — Craig ABSTAIN: COUNCIL MEMBERS — None OLIVIA NASHED City Clerk 2023-22