AGENDA TITLE: Specifications and Advertisement for Bids for Polemount
Transformers
MEETING DATE: January 19, 2000
PREPARED BY: Electric Utility Director
RECOMMENDED ACTION: That the City Council approve the specifications and authorize the
advertisement for bids for thirty-two conventional polemount
transformers in the following sizes:
10 each 25KVA 1201240V
15 each 37.5KVA 120/240V
7 each 50KVA 120/240V
BACKGROUND INFORMATION: These transformers will be used to replenish the Department's
inventory for the 2000 peak load season.
FUNDING: Electric Utility Department's Operating Budget
Estimated Cost: $29,000
BID OPENING: February 23, 2000
J
Prepared by Joel Harris, Purchasing Officer
c: Manager, Electric Utility Engineering and Operations
APwtovm:
TRANSFMR
Alan N. Vallow, Electric Utility Director
H. Dixon Flynn — City Manager
01/11/00
SPECIFICATIONS
POLEMOUNTED TRANSFORMERS - OIL FILLED
DIVISION 1 - GENERAL REQUIREMENTS
1-1 GENERAL
Electrical design and materials shall conform to the latest EEI-NEMA and ANSI Standards.
It is the intent of these specifications to describe equipment of the best design and
construction, for the service for which it is intended. Consequently, it shall be the City's
desire to award contracts to the bidder who has demonstrated high quality by having a
considerable number of transformers of bidder's manufacture in service on the lines of
electrical utilities over a period of years.
1-2 TESTS
Transformers shall receive at least the following tests in accordance with the applicable
ANSI and NEMA Standards:
(1)
Load and no-load loss
(5)
Applied and induced potential test
(2)
Exciting current
(6)
Impulse voltage test
(3)
Polarity check
(7)
Tank pressure test
(4)
1-3 SERVICE
Ratio check
The manufacturer shall own and operate a service shop in this vicinity, or the bidder may
submit evidence of a repair contract with an approved service shop in this vicinity, which
has been in effect for a period of at least one year. (For the purpose of this specification,
"vicinity" shall mean within a 200 -mile radius of the City of Lodi).
1-4 GUARANTEE
The Manufacturer shall guarantee all equipment delivered under these specifications
against any and all defects in material and/or workmanship for a period of at least one year
from date of acceptance. Manufacturer shall rectify all such defects by repair or
replacement at manufacturer's sole expense and shall assume responsibility for associated
shipping costs.
1-5 TECHNICAL INFORMATION
The following specifications shall be met:
Insulation level: 95 kv BIL (min).
2. Insulation rating: 65 0 C rise.
3. Rain : All exterior surfaces shall be painted ANSI 70 gray, using a system
of coordinated and thoroughly tested materials and application techniques
that will assure long life. Special attention shall be given to welds, seams,
edges and rough spots.
4. Lifting Lugs: Lifting lugs shall be provided on the tank and shall be located
HAUSERW DMINISPECSIPOLEXFRM.BK!
POLEMOUNT TRANSFORMERS - OIL -FILLED Sec. 1 Pg. 1
General Requirements
in such a way to avoid interference between lifting slings and any
attachments on the transformer and to avoid scratching the transformer
coating.
5. Tank: Tanks shall be tested at a pressure equal to or greater than the
maximum operating pressure and for a sufficient period of time to insure
that all welds are free from leaks. Tank construction shall be consistent with
good manufacturing and design practices prevalent in the transformer
industry, and together they should contribute to a high quality product.
6. Nameplate: Stainless steel or anodized aluminum nameplate shall be
securely attached to the transformer by means of metal screws, rivets, or
similar mechanical device(s). The letters and numbers shall be stamped or
engraved on the nameplate. The nameplate shall include the words, "Fluid
is less than one p.p.m. PCB," (refer to Section 1-7). The instruction
nameplate shall contain the information specified in Section 5.12 of ANSI
C57.12.00-1980.
7. Sound Level: The sound level shall be equal to or better than EEI-NEMA
Standards.
8. atgL Size of the transformer, including radiators (fins), shall not interfere
with installation or G.O. 95 requirements when banked together on cluster
bracket (Dixie Electric P-538 or approved equal).
9. Height and Weight: Height and weight of the transformer shall be as listed
below:
10. Pressure Relief Valve: The pressure relief valve shall be located a minimum
horizontal distance of five (5) inches from the vertical centerline of the
transformer hanger brackets.
Size (KVA)
Maximum Weight (lbs)
Maximum Height
(inches)
including bushings
15
400
45
25
500
45
37.5
625
48
50
800
51
75
1,100
51
100
1,200
51
167
1,600
51
M:IUSERW DMIMSPECSIPOLEXF RM. BKI
POLEMOUNT TRANSFORMERS - OIL -FILLED Sec. 1 Pg. 2
General Requirements
1-6 LOSSES
Losses will be considered in the evaluation of this bid as follows:
No-load (core) loss @ $6.00/watt
Load (winding) loss @ $2.00/watt
The cost of losses will be added to the equipment price (bid price) F.O.B: Lodi, including
maximum escalation and tax, to determine the evaluated low bid of vendor otherwise
meeting these specifications. All bidders shall supply the following guaranteed loss data
for use in the evaluation, in addition to other data listed in the specifications:
No-load losses in watts at rated secondary voltage.
2. Load losses in watts at rated secondary voltage and rated load. The
standard reference temperature for load losses shall be 850C.
3. Upon request, furnish certification/statement of the guaranteed loss
measurement error of the test equipment and measurement method to be
used, including the basis for determination of the accuracy of the test
equipment and measurement method.
The successful bidder shall supply a certified test report of actual losses of the unit(s) to be
supplied. The no-load and load losses for each group (type and size) of transformer(s) will
be averaged separately within their respective categories (no-load and load losses). If the
averaged tested no-load (core) and/or load(winding) losses of the transformer group
exceed the watt losses quoted in the proposal, the contract price shall be reduced by the
above amounts per watt of actual group averaged no-load and/or actual load loss in excess
of that quoted in the proposal. No-load loss penalties will be evaluated separately from load
loss penalties. No additional payment will be made to the manufacturer or bidder for actual
losses lower than the losses quoted in the proposal.
Certified test report of losses shall be submitted by the manufacturer prior to or at the time
of shipment of the transformer.
1-7 PCB CONTENT
Transformer fluid shall be guaranteed to contain less than one p.p.m. by weight (mg/kg)
polychlorinated biphenyls (PCB). Certified test report of PCB content shall be produced
upon request. The transformer nameplate shall include the words " Fluid is less than one
P.P.M. PCB."
H: W SER%ADM INISPECS%POLEXFRM. BK!
POLEMOUNT TRANSFORMERS - OIL -FILLED Sec. 2 Pg. 1
General Requirements (continued)
DIVISION 2 - SINGLE PHASE
2-1 GENERAL
In addition to that specified in Division 1 - General Requirements, transformers shall be
provided with the following:
1. High Voltage Bushings (Porcelain):
a. Quantity: Two
b. Bushing terminals to be clamp -type suitable for use with copper and
aluminum conductor.
2. Low Voltage Bushings:
a. Quantity: 277 -volt: Two
All others: Three
b. Shall be tank wall -mounted.
c. Bushing terminals: 100KVA and lower: Shall be clamp -type suitable
for use with copper and aluminum conductor.
Over 100KVA: Shall be NEMA -4 pads (4 -hole)
3. Pressure relief valve: Qualitrol 202-030-01, or an approved equal.
4. Lifting lugs shall be welded to the tank.
5. Provide tank grounding pad and a visible tank -to -cover ground strap.
6. Hanger brackets, welded to the tank.
7. Hanger brackets shall permit bolting of transformer directly to pole.
8. Single phase, 60Hz, DISC.
2-2 RATINGS AND DESIGN
Transformers shall have the following ratings and design:
1. Distribution type, pole -bolted transformer.
2. 12,000 -Volt Delta primary.
3. Single phase
4. Without arresters and taps.
5. Conventional or CP type as specified on proposal form. CP transformers to
have one weak link (fuse) per primary bushing and a breaker on the
secondary side.
6. Secondary voltage to be as specified on the proposal form.
7. KVA rating to be as specified on the proposal form.
M. XUSER%ADMIMSP ECSIPOLEXFRM. BK!