HomeMy WebLinkAboutOrdinances - No. 520In the City Council
City of Lodi
Lodi, California
ORDINANCE NO. 520
ADOPTING RULES AND REQUIREMENTS GOVERNING
THE INSTALLATI ON OF ELECTRICAL METERS.
The City Council of the City of Lodi does ordain as
follows :
Section 1. GENERAL: These rules cover the details of EX0
type installations only.
switchboards shall comply with the minimum requirements of the
Western Utilities Electric Service Standardization Committee.
For further information regarding switchboards, please consult
the Utilities Department of the City of Lodi, California.
The details for the arrangement of
All meter installations shall comply with the minimum re-
quirements contained herein and with rules and regulations of
the inspection authorities having jurisdiction.
If any question arises for which you cannot find the answer
in the following pages, it is suggested that you call the Utilities
Department of the City of Lodi, 8-0641, for such further infor-
mat ion.
Whenever any electrical wiring of Class I, as defined in the
City of Lodi Electrical Code, is installed, provision shall be
made for the installation of metering equipment complying with
these service requirements, except when there is existing metering
equipment which, in the opinion of the Electrical Inspector of
the City of Lodi, is satisfactory and adequate to register all
electric current to be supplied.
When a property owner is permitted to do his own wiring he
will be considered the electrical contractor for the purpose of
these requirements.
-1-
Section 2. SERVICE ENTRANCE REQUIREMENTS: The service
entrance head or outlet shall be located in accordance with
Section 2324 of the National Electrical Code as interpreted by
the City of Lodi.
the point of service attachment, if possible, to preclude the
possibility of water entering the service conduit or cable and
ultimately the meter. The customer's service entrance wires
shall extend two feet beyond the service head or outlet and thus
be long enough to provide for drip loops and attachment to the
service drop.
The service head should be placed higher than
In these requirements the capacity of the service switch has
been used as the basis for determining the size of other related
equipment. In those cases where a main service switch is not
used,the current carrying capacity of the service entrance conduc-
tors shall be considered as the service switch capacity.
Section 3. METER SEQUENCE: The metering arrangements re-
quired by the Utilities Department of the City of Lodi provide
for the line current to enter first the meter and then the dis-
connect and overload protective devices.
Section 4. TYPE OF METERING INSTALLATION: Provision shall
be made for the installation of a self-contained meter (no instrument
transformers) under the following conditions:
(d) If the capacity of the service switch does not
exceed 100 Amps, on commercial application, or 200 Amps
on domestic application.
(b) For power loads if the connected load does not
exceed 30 h.p. and the voltage is 300 volts or less.
In all other cases provision shall be made for the instal-
lation of instrument transformers and a transformer-type meter.
For large installations the Utilities Department, City of Lodi,
should be consulted to determine if provision is necessary for
installation of a varhour meter to measure power factor.
Socket type meters will be used on all installations.
- 2-
Section 5. METER SOCKETS: The contractor shall install
meter sockets in accordance with the following table:
SELF-CONTAINED METERS
No. of Jaws
TvDe of Service in Socket
Single-phase 2 wire, 120 or 240 v. 4 Single-phase 3 wire, 120/240 V. 4
Single-phase 3 wire, 120/208V. wye 5
Three-phase 3 wire 5
Thr ee-phas e 4 wire delta 7
Three-phase 4 wire wye 7
Sockets for self-contained meter shall be installed and wired
by the contractor.
Section 6. INSTRUMENT TRANSFORMER INSTALLATIONS : An instru-
ment transformer installation consists of metering current or
potential transformers, or both, mounted in a metal cabinet and
a watthour meter with its accompanying test facilities. For large
loads a varhour meter is required in addition to the watthour meter.
The Utilities Department, City of Lodi, will furnish and
install the secondary wiring from the instrument transformers
to the meter in conduit or raceways furnished and installed by
the contractor.
meter test blocks or test switches, trhich will also be furnished
by the b'aiti'Utikii?ies*DepaPtment.
Provision must be made for the installing of
The contractor shall furnish and install a metal cabinet
for housing the metering instrument transformers in accordance .
with the following specifications. The sizes tabulated below
are minimum requirements which are acceptable to the Utilities
Department, City of Lodi.
MINIMUM INSTRUMENT TRANSFORMER CABINET SIZES
208 Volt, 4-Wire, or
Service Switch 240 Volt 480 Volt, +Wire CaDac i tv +Wire Service Service
200 Amp. 24x24~10 *I 24x36~10" 400 Amp. 24~36x10 ** 36~36x10~~ 600 hp. 24x36 x10 3 6 x3 6 x10 800 hp. 36 x48 xl0 It 36~48x10~~
-3-
When a service switch larger than 800 Amps. is to be used
in this type of installation, the Utilities Department, City
of Lodi, should be consulted to determine the cabinet size.
In all cases provision shall be made for sealing the cabinet
by the use of padlock-type seals.
All covers which must be lifted into place should be equipped
with two handles or similar lifting devices. All covers shall
have a small caution sign on the front saying, "DO not break
seals. No fuses inside."
Instrument transformer cabinets may be mounted either indoors
or outdoors, provided that outdoor installations shall be rain-
tight. Cabinets may be mounted either horizontally or vertically
at the customer's option, provided that the cables shall enter
and leave the cabinet in such a manner that the Utilities Depart-
ment can conveniently install and connect the trqnsformers.
Sufficient length of meter loop conductors shall be left
to connect to current transformers. A meter loop conductor is
defined as a wire or cable extending into the cabinet for con-
nection to the primary of a metering current transformer.
Section 7. MULTIPLE METER INSTaLATIONS:
(a) When a building has more than one customer or more
than one type of service it is necessary to use a multiple
meter installation. Won-switchboard multiple occupancy in-
stallations can usually best be arranged by utilizing a meter '
trough. Standardized meter troughs using ring-type sockets
or individual sockets in combination with standardized wire
gutters or their equivalent are recommended. Troughs and
wire gutters containing unmetered wiring shall always be
provided with two studs having 1/16ii holes for sealing in
addition to the screws normally used to hold the cover in
place. Unmetered service wires and metered load wires shall
not be run in the same conduit, raceway, or wiring gutter.
-4-
(b) The rules for spacing of multiple meter installa-
tions using socket-type meters shall be as follows:
Horizontal indoor installations--10 inehes minimum on
centers.
Horizontal outdoor installations--?* inches minimum
on centers
Vertical indoor or outdoor installations--8$ inches
minimum on centers.
The above spacings are satisfactory for all socket-type
meter installations with the exception of three-phase, four-
wire services. For this type of installation, it is strongly
recommended that the Utilities Department, City of Lodi,
be consulted for each individual case in order to determine
proper spacing.
(c) When using meter troughs on multiple occupancy in-
stallations, the use of bus line terminals on the meter
sockets is recommended. Not more than three meters shall
be mounted on a single front panel of a meter trough.
I)i$ cast sockets shall not be used as a wiring gutter
for more than two meters. Care should be exercised on this
type installation that metered and unmetered wiring does not
occupy the same conduit. Wire larger than No. 2 AWG shall
not be used in die cast sockets.
(d) In multiple occupancy buildings or multiple build-
ing properties all the meters shall be mounted at a common
location adjacent to the street. Where one or more meters
are added to an existing installation, they shall either
conform to the existing plan, or the existing meters shall
be rearranged to conform to a new plan.
(e) Cabinets designed for installation of meters and
service switches shall be 12 inches deep. Care should be
exercised to design a cabinet so that neither the roof nor
the door supports will interfere with installation of the
meter. With the cabinet door open, a clear space of at
- 5-
least 15 inches directly in front of the socket is required
to insert the meter in the socket.
(f) Each meter position in multiple meter installations
shall be clearly and prominently marked in a permanent manner
by the contractor to indicate the particular location supplied
by it.
c om pl e t e .
Meters will not be installed until the marking is
In case of multiple dwellings where one building includes
six apartments or less, the markings shall be such that, facing
the building from the street, the apartment designation will
be "Lower Right", "Lower Left", "Lower Rear Left", %'Lower
Middle", "Upper Front Right", etc. In case of multiple dwell-
ings of seven apartments or more, each meter switch shall
be marked by letter or numeral to correspond to the apartment
it serves.
Section 8. METER LOCATIONS : Electric meter installations
shall :
(a) Be located so as to be accessible to authorized
representatives of the Utilities Department, City of Lodi,
for reading, test and inspection at all reasonable times.
Outdoor meter locations are preferred.
(b) Not be located in any of the following places:
(1) On any floor higher than the ground floor.
(2) In any place where moisture, fumes or dust
may interfere with its operation or materially
damage the meter.
In any elevator shaft or hatchway. (3)
(4) In any hazardous location.
(5)
(6) Directly over any stairway, ramp or steps.
(7)
In any place not in general use.
On any surface subject to excessive vibration,
as determined by the Utilities Department.
(8) In any doorway.
(9) On or recessed in the external surface of any
wall or any building that is built within 3
feet of any property line or on the line of
any walk, alley or driveway giving access to
commercial or industrial property, except
when permitted by the Utilities Department.
On any portion of a building which might at
a later date be enclosed and thus make the
meter inaccessible. Examples of these locations
are carports, breezeways, covered porches, etc.
(10)
Since meters are sometimes noisy, it is recommended that
locations on exterior walls of bedrooms or bedroom closets be
avoided if possible.
Section 9. METER HEIGHTS: Meters shall be located not more
than 75 inches and not less than 66 inches above the ground or
standing surface when installed outdoors. When installed outdoors
in a cabinet or indoors in a meter room, the minimum height may
be reduced to 36 inches.
In the event special permission is granted to locate a meter
adjacent to a walk or driveway (see METER LOCATIONS, b-91, it
should be mounted 84 inches above such walk or driveway. However,
in no event shall a demand meter be mounted higher than 75 inches.
Section 10. WORKING SPACE: A level standing and working
surface shall be pcroirtded in front of each metering installation.
A clear and unobstructed working space shall be provided above
this surface. The width of the working space shall be sufficient
to permit ready access to the metering equipment and in no case
less than 3 feet. The height of the working space shall be equal
to the over-all height of the metering ins-tallation and in no case
less than 6 feet. The working space shall extend at least 3 feet
from the surface on which the metering equipment is mounted.
Section 11. DISCONNETING AND CONNECTING METERS: Under no
circumstances will an electrical contractor or any one other than
an employee of the Utilities Department, City of Lodi, be allowed
to break a seal on the UtilityPs meter, or connect or disconnect
a meter.
Section 12. PENALTIES: Any person, firm or corporation
violating any of the provisions of this ordinance shall be guilty
of a misdemeanor and upon conviction thereof shall be punishable
by a fine of not more than Five Hundred Dollars ($500.00) or by
imprisonment in the City Jail for a period of not more than six
(6) months, or by both such fine and imprisonment.
Section 13. VIOLATIONS: fiery person, firm or corporation
violating any of the provisions of this ordinance shall be deemed
guilty of a separate offense for each day or portion thereof during
which such violation continued and shall be punishable therefor
as herein provided.
Section 14. PROHIBITIONS: It is unlawful for any person,
firm or corporation, either as owner, architect, contractor, artisan
or otherwise, to do or knowingly to cause or permit to be done
any electrical wiring as defined in this ordinance in such manner
that the same shall not conform to all of the provisions of this
ordinance.
Section 15. This ordinance shall be published one time in
the "Lodi News-Sentinel", a newspaper of general circulation
printed and published in the City of Lodi, and shall be in force
and take effect thirty days from and after its passage.
Approved this 2nd day of February , 1955.
Mayor of the City of Lodi
ATTEST :
HENRY A. GLAVES , JR.
City Clerk
-8-
I, tiEi\KY A. GLhVhS, JR., City Clerk of the Gity of Lodi
and ex officio Clerk of the City Council of said City, do
hereby certify that the foregoing Ordinance No. 520 was intro-
duced in regular meeting of said Council held January 5, 1955,
and was thereafter passed, adopted and ordered to print at a
regular meeting of the City Council held February 2, 1955, by
the following vote:
AYES: Councilmen - Hughes, hitchell, nobinson and Fuller
NOES: Councilmen - None
ABSENT: Councilmen - dichey
I FURTHER CERTIFY ghat Ordinance No. 520 was approved and
signed by the Mayor on the date of its passage and has been
published pursuant to law. &a HENH A. GLAVLS’. kJ El.
City -Clerk v
Dated: February 18, 1955