SUBJECT: SPECIFICATIONS AND ADVERTISEMENT FOR BIDS FOR THE PURCHASE OF PRIMARY OVERHEAD.
PRIMARY UNDERGROUND, AND SECONDARY UNDERGROUND ELECTRICAL CABLE
RECOMMENDED ACTION: That the City Council approve the specifications
and authorize the advertisement for bids for the purchase of various
sizes of overhead and underground conductor as detailed below:
Primary Overhead Conductor
#4/0 Bare Aluminum 14,000 feet
#477 Bare Aluminum 45,000 feet
15KV Concentric Primary Under4round Conductor
#2AWG, Jacketed 25,000 feet
#2/OAWG 20,000 feet
#750 KCM 20,000 feet
#1000 KCM, Jacketed 22,000 feet
Secondary Underground Conductor
#350 KCM Triplex 20,000 feet
BACKGROUND INFORMATION:- The overhead conductor is being purchased to
support planned distribution system improvements budgeted for this
fiscal year, and to provide an inventory of cable to cover other needs
as they develop. The improvements are expected to require about 12,000
feet of #4/0 and 33,000 feet of #477 conductor.
The underground primary cable is being purchased to support projects in
the Sunwest subdivisions, the Kettleman Lane/Lower Sacramento Road
development, at the substations, and in budgeted distribution system
improvements. These specific needs are expected to take about 15,000
feet of #2AWG, 7,000 feet. of #2/OAWG, 10,000 feet of #750KCM, and
16,000 feet of #1000KCM. The balance of the quantities purchased would
provide an inventory tc cover other requirements as they develop.
The #350KCM Triplex is being purchased mainly to re-establish a working
inventory, although abou.: 3,000 feet is planned for use in the Sunwest
subdivisions.
The anticipated cost of this purchase is about $235,000; funding is
available in the Electric Utility Department's Operating Fund.
The bid opening date has been set for Tuesday, January 16, 1990.
74 e,.
J . Harris,
P61rchasing Officer
cc: Electric Utility Directcr
Assistant Electric Utility Director
Electrical Engineer
EQUIPMENT SPECIFICATION
OVERHEAD CONDUCTORS, 477.0 KCM, BARE ALUMINUM AAC
This specification is for stranded aluminum overhead conductor, suitable
for use in the City of Lodi's 12.0 kv overhead distribution system.
SPECIFIC SPECIFICATIONS:
477.0 KCM all aluminum conductor (AAC), 19 strand, Class AA. Code Name: COSMOS.
�y 110 ��NRE
The conductor shall meet the requirements of the latest edition of the
applicable NEMA, ASTM and ANSI standards, unless otherwise noted in this
specification.
Conductor to come in reels of 8,000 feet (nominal). Each end of the conductor
shall be firmly secured to the reel. No lagging is required. All shipments
shall be prepaid, F.O.B. Lodi, Califorsia. Reels shall be shipped upright.
REEL MARKING:
Each reel shall be marked with a durable label securely attached to a
flange of the reel and plainly marked stating the destination, the purchaser's
order number, shipping length of conductor on reel, weight of reel (tare
weight), total weight of the conductor on reel, type and size of conductor
and code name.
MAKE UP AND LENGTHS:.
NEMA standard code reel #6628 (66 in. flange diameter, 28 in. traverse width)
shall be used. Conductor length on each reel shall be 8,000 feet (nominal).
ENGINEERING STANDARD
C17Y OF LO D I OVERFiF2.D CONDUCTOR, PRIMARY, 477.0 KCM
ELECTRIC UTILITY DEPARTMENT
ATE DRAWN CHECKED
a!�-� SKEET OF J
APPROVAL REVISION
CITY OF LODI ELECTRIC UTILITY DEPARTMENT
13 I1 IENI SPECIFICATIONS
15 -KV, XLPE IlqRJLATM, JACK=, CONCENTRIC NEUTRAL CABLE
1.0 GENERAL
Cable furnished under these specifications shall be limited to
cross-linked thermosetting polyethylene (XLPE) insulated concentric
neutral cable rated 15,000 volts and suitable fcr installation in ducts or
for direct burial in earth, in wet or dry locations, with normal conductor
temperatures up to 90°C. Cables furnished shall meet the requirements of
the applicable NEMA, ICEA, ASIC and ASTM Standards, latest edition
thereof, unless otherwise noted in this Specification.
2.0 CABLE
A. Conductor
Insulated conductor shall be aluminum alloy, EC Grade, Class B
standard or compressed strand, three-quarter or half hard.
B. Conductor Shield
The conductor (strand) shielding shall be extruded and shall consist
of virgin black semi -conducting cross -1 inked, thermosetting
polyethylene. The extruded shield shall have an average thickness of
not less thar 15 mils when measured over the top of the strands and a
minimum thickness of not less than 12 mils. The outer surface of the
conductor shield shall be cylindrical and shall be firmly bonded to
the overlaying insulation.
S-1 12/12/89
S/CABLEX/TXTU.01D
C. Insulation
Insulation shall be unfilled, semi -transparent, cross-linked
polyethylene extruded directly over the conductor shield. The average
insulation thickness shall not be less than 220 mils and the minimum
thickness shall not be less than 50%of this value.
D. Insulation Shield
The insulation shielding shall be extruded and shall consist of one
layer of virgin black semi -conducting polyethylene or semi -conducting
cross-linked polyethylene, compatiblr, with and extruded over the
i ns,:l ati on. It shall maintain its shielding properties after exposure
to normal operating temperatures and environs. The thickness of tj,a
insulation shield shall be in accordance with Table I below.
TABLE I
Thickness of Extruded Insulation
Shield (Mils)
Diameter of Care (Inches) Average NIUMMUM
0 - 1.000 3G 24
1.00.1 - 1.500 50 40
1.501 - 2.000 70 56
E. Construction Method
Conductor shield, insulation and insulat on shield sha 1 be installed
on the conductor using the triple extruding, dry cure me :hod.
F. Concentri c Neutral
The concentric conductor
shall be composed of
a number of round
annealed
bare (uncoated)
copper wires helically
wrapped around the
cable.
The number and size
of the neutral wires
shall be as spec,fied
in Table
I I . The length of
lay shall not be less
than 6 nor more than
10 times
the diameter over
the concentric wires.
S-2 12/12/89
S/CABLEX/TXTU.OID
G. Testing and Guarantee
Testing of cable shall be performed according to procedures set forth
by the ICEA, AEIC and ASTM Standards. Certified copies of pass/fail
test results shall be supplied. Any cable found defective either upon
inspection, testing or installation will be returned at the
manufactorer's expense.
H. Overal' Jacket
An extruded, encapsulating and insulating layer of linear, low density
black polyethylene, (Union Carbide DFDB 6425 or approved equivalent)
shall be applied over the concentric neutral wires i n . accordance with
ICEA 5-66-524, Part 4.3, except where modified by this Specification.
The minimum thicknesses of this encapsulating jacket over the
concentric wires are as follows:
Conductor Size
(,AWG or KCWI
82
#2/0
750 & 1,000
Minimum Thickness
�Milcl�
50
80
110
1. Specific Requirements
Any conditionsl bids such as "subject to availability in stock" will
be rejected. Cable shall be furnished according to Table II below:
TABLE II
Conductor Size
Conc. Neutral
NEMA
AWG or
KCM
Size - AWG
Material
Insulation
Real Code
(No. of
Strands)
(Min. No. of Wires)
Phase
(Neat.)
Thick. (Mils)
Number
12
(7)
f14 (10)
Alum.
(Cu)
220
5832
#2/0
(19)
#14 (9)/#12 (6)
Alum.
(Cu
220
5832
750
(61)
f12 (24)/010 (15)
Alum.
(Cu)
220
7848
1,000
(61)
#10 (20)
Alum.
(Cu)
220
7848
NOTE: Refer to proposal forms for specific sizes and quantities.
5-3 12/12/89
SiCABLEX/TXTU.OID
J. Reels
1. Makeup and Lenath:
Cable length on each reel shall be in accordance with Table III
be 1 ow:
TABLE III
Conductor Size (AWG cr KCM)
Cable Length (Feet)
#2
4,000 ± 4%
#2/0
2,500 ± 4%
750
2,500 ± 40%
1,000
2,000 ± 4%
2. Packaping:
Each cable reel shall
have
adequate
protective covering across the
flanges. Such covering
to
consist
of wood members from flange to
flange cc'.ering the
entire
circumference
of the reel (lagging).
The lagging shall be
nailed
to the
flange perimeters and shall be
further secured with
at least two
steel bands around the reel.
Each end of the cable
shall
be firmly
secured to the reel.
3. Marking:
Each reel shall be marked with a durable label securely attached
to a flange of the reel and plainly marked stating the -
destination, the purchaser's order number, shipping length of
cable on reel , weight of reel (tare weight), total weight of cable
on reel, type and size o f conductor, insulation type and
thickness, voltage rating and manufacturer's identification number.
K. Shipping
Cable ends shall be adequately sealed with a water seal -type material
and plastic end caps secured by tape to prevent the penetration of
moisture. There shall be no water in the stranded conductor of the
5-4 12/12/89
S/CABLEX/TXTU.CiC
cable Wm the reel is stripped. Reels shall be shipped upright. All
shipments shall be prepaia, F.O.B. Lodi, California.
s-5 12/12/89
5/CRBLEX/TXTU.0IU
EQUIPMENT SPECIFIuATIONS
600 -VOLT XLPE TRIPLEX CABLE
101:4010:7_1m
CABLE FURNISHED UNDER THESE SPECIFICATIONS SHALL BE LIMITED TO
CROSS-LINKED POLYETHYLENE INSULATED CABLE RATED 600 VOLTS AND SUITABLE
FOR INSTALLATION IN DUCTS OR FOR DIRECT BURIAL IN EARTH, IN WEE OR DRY
LOCATIONS, WITH NORMAL CONDUCTOR TEMPERATURES UP TO 90 DEGREES C.
CABLES FURNISHED SHALL MEET THE REQUIREMENTS OF THE APPLICABLE NEMA,
ICEA, AEIC AND ASTM STANDARDS, LATEST EDITION THEREOF, UNLESS OTHERWISE
NOTED IN THIS SPECIFICATION.
CABLE:
A. CONDUCTOR:
THE CONDUCTOR SHALL BE ALUMINUM ALLOY, EC GRADE, 1/2 TO '/4 HARD,
CLASS B STRANDING.
B. INSULATION :
PHASE CONDUCTOR INSULATION SHALL BE SINGLE -PASS, BLACK, CROSS-LINKED
POLYETHYLENE. THE NEUTRAL CONDUCTOR SHALL HAVE YELLOW XLPE INSULATION
OR BLACK XLPE INSULATION WITH YELLOW EXTRUDED STRIPES.
C. ASSEMBLY:
THE ASSEMBLED CABLE SHALL CONSIST OF PHASE AND NEUTRAL CONDUCTORS
TWISTED TOGETHER WITH A LAY NOT LESS THAN 50 NOF MORE THAN 60 TIMES THE
OUTSIDE DIAMETER OF ONE OF THE PHASE CONDUCTORS- ALL CABLE ENDS SHALL
BE SEALED TO PREVENT THE ENTRFNCE OF MOISTURE.
D. IDENTIFICFTION:
EACH CONDUCTOR SHALL HAVE A PERMANENT MARKING SHOWING THE MANUFACTURER'S,
NAME, VOLTAGE RATING, CONDUCTOR SIZE AND TYPE GF INSULATION.
E. TESTING AND GUARANTEE:
TESTING OF CABLE SHALL BE PERFORMED ACCORDINr3 TO PROCEDURES SET FORTH
BY THE ICEA, AEIC AND ASTM. CEPTIFIED COPIES OF PASS/FAIL TEST RESULTS
SHALL BE SUPRL 7 ED. ANY CABLE FOUND DEFECTIVE EITHER UPON INSPECTION,
TESTING OR INSTALLATION WILL BE RETURNED AT THE MANUFACTURER'S EXPENSE.
F. SPECIFIC REGUIRE-MENTS:
CABLE SHPLL BE FURNISHED ACCORDING TO TPBLE 1 AS SHOWN BELOW. ANY
CONDITIONAL BIGS SUCH AS "SUBJECT TO AVAILABILITY IN STOCK" WILL BE
REJECTED.
G. SHIPPING:
CABLE ENDS SHALL BE ADEQUATELY SEALED WITH A WGTER SEAL -TYPE MATERIAL
AND PLASTIC END CAPS SECURED EY TAPE TO FREVENT THE PENETRATION OF
MOISTURE. THERE SHALL BE NO WATER IN THE STRANDED CONDUCTOR OF THE
CABLE V*EN THE REEL IS SHIPPED. ALL SHIPMENTS SHALL EE PREPAID,
F.O.B. LODI, CALIFORNIA. REELS SHALL EE SHIPPED UPRIGHT.
REELS:
A. MAKEUP AND LENGTH:
THE SPECIFIED CONDUCTOR' SHALL EE SUPPLIED ON NEMA STANDARD HEELS IN
ACCORDANCE WITH TABLE 1_
B_ PACKAGING:
EACH CPFLE REEL SHALL HAVE ADEQUATE PROTECTIVE_ COVERING ACROSS THE
FLANGES, SUCH COVERING TC CONSIST OF WOOD MEMBERS FROM FLANGE TO FLANGE
COVERING THE ENTIRE CIRCUMFERENCE OF THE REEL (LAGGING), THE LAGGING
SHALL BE NAILED TO THE FLFNGE PERIMETERS AND SHALL BE FURTHER SECURED
WITH AT LEAST TWO STEEL BANDS AROUND THE REEL. EACH END OF THE CABLE
SHALL RE FIRMLY SECURED TO THE REEL.
C. MARKING:
EACH REEL SHALL BE MARk'ED WITH A DURABLE LABEL SECURELY ATTACHED TO A
FLANGE OF THE REEL Alv7 F LA I NY MARtCE i7 -TATI N(-3 THE DESTINATION, THE
PURCHASER'S ORDER NUMBER, SHIPPING LENGTH OF CABLE ON REEL, TYPE AND
S I ZE OF C� !NOL:cT� :RS , INSULATION TYPE AND THICKNESS, VOLTAGE RATING AND
MANUFAC T '_}RER ' S I DENT I F I CATION NUMBER.
CONDUCTOR SIZE i CODE WORD
MATERIAL
NEMA STANDARD
PHASE (NEUTRAL)
REEL CODE NO.
i
#2 (#2) AWG
RAMAPO/YES
ALUM.
3624
#1/0 (#i/0) AWG
BERGEN/YES
ALUM.
3424
350 MCM (#4/0) AWG
WF_SLEYANtYES
ALUM.
7736
G. SHIPPING:
CABLE ENDS SHALL BE ADEQUATELY SEALED WITH A WGTER SEAL -TYPE MATERIAL
AND PLASTIC END CAPS SECURED EY TAPE TO FREVENT THE PENETRATION OF
MOISTURE. THERE SHALL BE NO WATER IN THE STRANDED CONDUCTOR OF THE
CABLE V*EN THE REEL IS SHIPPED. ALL SHIPMENTS SHALL EE PREPAID,
F.O.B. LODI, CALIFORNIA. REELS SHALL EE SHIPPED UPRIGHT.
REELS:
A. MAKEUP AND LENGTH:
THE SPECIFIED CONDUCTOR' SHALL EE SUPPLIED ON NEMA STANDARD HEELS IN
ACCORDANCE WITH TABLE 1_
B_ PACKAGING:
EACH CPFLE REEL SHALL HAVE ADEQUATE PROTECTIVE_ COVERING ACROSS THE
FLANGES, SUCH COVERING TC CONSIST OF WOOD MEMBERS FROM FLANGE TO FLANGE
COVERING THE ENTIRE CIRCUMFERENCE OF THE REEL (LAGGING), THE LAGGING
SHALL BE NAILED TO THE FLFNGE PERIMETERS AND SHALL BE FURTHER SECURED
WITH AT LEAST TWO STEEL BANDS AROUND THE REEL. EACH END OF THE CABLE
SHALL RE FIRMLY SECURED TO THE REEL.
C. MARKING:
EACH REEL SHALL BE MARk'ED WITH A DURABLE LABEL SECURELY ATTACHED TO A
FLANGE OF THE REEL Alv7 F LA I NY MARtCE i7 -TATI N(-3 THE DESTINATION, THE
PURCHASER'S ORDER NUMBER, SHIPPING LENGTH OF CABLE ON REEL, TYPE AND
S I ZE OF C� !NOL:cT� :RS , INSULATION TYPE AND THICKNESS, VOLTAGE RATING AND
MANUFAC T '_}RER ' S I DENT I F I CATION NUMBER.