AGENDA TITLE: Specifications and Advertisement for Bids for
Electrical Cable for the Electric Utility Department
MEETING DATE: November 18, 1992
PREPARED BY: Electric Utility Director
RECOMMENDED ACTION: That the City Council approve the specifications
and authorize advertisement for bids for the
purchase of 30,000 feet of #2/0 15kV underground
primary conductor, and 10,000 feet of 600 -volt
secondary triplex for the Electric Utility Department.
BACKGROUND INFORMATION: This cable will be needed for installation in eleven
new residential and commercial subdivisions sched-
uled to begin during the next six to twelve months,
and to provide an inventory for routine or emergency
maintenance of the existing electrical system.
Some of the developments where this cable will be used are Sunwest Plaza 2,
Johnson Ranch 2, Century Meadows 1, 2, and 3, Towne Ranch 1, and the new
Target store. As home construction continues beyond the 12 -month horizon,
additional 600 -volt triplex will be needed, and bids will be solicited at
that time.
FUNDING: Included in the Electric Utility Department's
1992/93 fiscal year budget.
Estimated cost: $40,000
BID OPENING DATE: December 22, 1992
Henry J. FTc�`ctric Utility director
Prepared by Joel Harris, Purchasing Officer
APPROVED
THOMAS A. PETERSON .ecvUeO P9Der
City Manager
cc
EDUIPMENT SPECIFICATIONS REV. 4/10/90
600 -VOLT XLPE TRIPLEX CABLE
GENERAL:
CABLE FURNISHED UNDER THESE SPECIFICATIONS SHALL BE LIMITED TO
CROSS-LINiED POLYETHYLENE INSULATED CAFLE RATED 600 VOLTS AND SUITABLE
-OR INSTALLATION IN DUCTS OH FOR DIRECT BURIAL IN EARTH, IN WET OR DRY
LOCATIONS, WITH NORMAL CONDUCTOH TEMPERATURES UP TO 90 DEGREES C.
CABLES FURNISHED SHALL MEET THE REQUIREMENTS OF THE APPLICABLE NEMA,
ICEA, AEIC AND ASTM STANDARDS, LATEST EDITION THEREOF, UNLESS OTHERWISE
NOTED IN THIS SPECIFICATION.
107-11144=F
A. CONDUCTOR:
' THE CONDUCTOR SHALL BE ALUMINUM ALLOY, EC GRADE, 1/2 TO 3/4 HARD,
CLASS B STRANDING.
R. INSULATION:
PHASE CONDUCTOR INSULATION SHALL BE SINGLE -PASS, BLACK, CROSS-LINKED
POLYETHYLENE. THE NEUTRAL CONDUCTOR SHALL HAVE YELLOW XLPE INSULATION
OH BLACK. XLPE INSULATION WTTH YELLOW EXTRUDED STRIPES.
C. ASSEMBLY:
THE ASSEMFLED CABLE SHALL CONSIST OF PHASE AND NEUTRAL CONDUCTORS
TWISTED TOGETHER WITH A LAY NOT LESS THAN 50 NOR MORE THAN 60 -IMES THE
OUTSIDE DIAMETER OF @NE OF THE PHASE CONDUCTORS. ALL CARLE ENDS SHALL
BE SEALED TO PREVENT THE ENTRPNCE OF MOISTURE.
D. IDENTIFICATION:
EACH CONDUCTOR SHALL HAVE A PERMANENT MARKING SHOWING THE MANUFACTURERS
NAME, VOLTAGE RATING, CONDUCTOR SIZE AND TYPE OF INSULATION.
E. TESTING AND GUARANTEE:
TESTING OF CABLE SHALL BE PERFORMED ACCORDING TO PROCEDURES SET FORTH
BY THE ICEA, AEIC AND ASTM. CERTIFIED COPIES OF PASS/FAIL TEST RESULTS
SHALL BE SUPPLIED. ANY CABLE FOUND DEFECTIVE EITHER UPON INSPECTION,
TESTING OR INSTALLATION WILL BE RETURNED AT THE MANUFACTURER'S EXPENSE.
PAGE. NO. I
F. SPECIFIC REQUIREHENTS:
ANY CONDITIONAL BIDS SUCH AS "SUBJECT TO AVAILABILITY IN STOCK" WILL BE
REJECTED.
G. SHIPPINC,,;
CABLE ENDS SHALL BE ADERUATELY SEALED WITH A WATER SEAL -TYPE MATERIAL
AND PLASTIC END CAPS SECURED BY TAPE TO PREVENT THE PENETRATION OF
MOISTURE. THERE SHALL BE NO WATER IN THE STRANDED CONDUCTOR OF THE
CABLE WHEN THE REEL IS SHIPPED. ALL SHIPMENTS SHALL BE PREPAID,
F.O.P. LODI, CALIFORNIA. REELS SHALL BE SHIPPED UPRIGHT:
REELS:
A. MAKEUP:
THE SPECIFIED CONDUCTOR SHALL BE SUPPLIED ON NEMA STANDARD REELS AND IN
ACCORDANCE WITH TABLE I AS SHOWN BELOW.
TABLE I
CONDUCTOR SIZE CODE WORD
FHASE (NEUTRAL)
HATERIAL
NEMA STANDARD
REEL CODE NO.
#2 f#2) AWG
RAMAPO/YES
ALUM.
3624
#i1/0 (#!/O) AWG
BERGEN/YES
ALUM. 7,624
350 MCM (#4/4) AWG
WESLEYAN/YES
ALUM.
5432 OR 7236
@ PACKAGING:
EACH CABLE REEL SHALL HAVE ADEQUATE PROTECTIVE COVERING ACROSS THE
FLANGES, SUCH COVERING TO CONSIST OF WOOD MEMBERS FROM FLANGE TO FLANGE
COVERING THE ENTIRE CTRCUKFERENCE OF THE REEL (LAGGING), THE LAGGING
SHALL. BE NAILED TO THE FLANGE PERIMETERS AND SHALL BE FURTHER SECURED
WITH AT LEAST TWO STEEL BONDS AROUND THE REEL. EACH END OF THE CABLE
SHALL BE FIRMLY SECURED TO THE REEL.
C. MARKING:
EACH REEL SHALL BE MARKED WITH A DURABLE LAPEL SECURELY ATTACHED TO A
FLANGE OF THE REEL AND PLAINY MARKED STATING THE DESTINATJON, THE
PURCHASER'S ORDER NUMEER, SHIPPING LENGTH OF CABLE ON REEL, TYPE AND
SIZE OF CONDUCTORS, INSULATION TYPE AND THICKNESS, VOLTAGE RATING AND
MAN(IFACTURFR •S I DENT i FI CAT I I N NUMBER.
PAGE NO. 2
CITY OF LODI ELECTRIC UTILITY DEPARTMENT
EOUIPMENT SPECIFICATIONS
15 -KY, XLPE INSULATED, JACKETED AND NON-JACKETED,
CONCENTRIC NEUTRAL CABLE
Cable furnished under these specifications shall be limited to
cross-linked thermosetting polyethylene (XLPE) insulated concentric
neutral cable rated 15,000 volts and suitable for installation in ducts or
for direct burial in earth, in wet or dry locations, with normal conductor
temperatures up to 90°C. Cables furnished shall meet the requirements of
the applicable NEMA, ICER, AEIC and ASTM Standards, latest edition
thereof, unless otherwise noted in this Specification.
2.0 CABLE
A. Conductor
Insulated conductor shall be aluminum alloy, EC Grade, Ciass 8,
stranded or compressed strand, three-quarter or half hard.
0. Conductor Shield
The conductor (strand) shielding shall be extruded and shall consist
of virgin black semi -conducting cross-linked, thermosetting
polyethylene. The extruded shield shall have an average thickness of
not less than 15 mils when measured over the top of the strands and a
minimum thickness of not Jess than 12 mils. The outer surface of the
conductor shield shall be cylindrical and shall be firmly cbonded to
the overlaying insulation.
S-1 11/06/92
S`CABLEX/TXTU.01D
C. Insulation
Insulation shall be unfilled, semi -transparent, cross-linked
thermosetting polyethylene extruded directly over the conductor
shield. The average insulation thickness shall not be less than 220
mils and the minimum thickness shall not be less than 90% of this
value.
D. Insulation Shield
The insulation shielding shall be extruded and shall consist of one
layer of virgin black semi -conducting, cross-linked thermosetting
polyethylene, compatible with and extruded over the insulation. It
shall maintain its shielding properties after exposure to normal
cDerating .--1pAratur�s ?nd environs. The insulation shield compound
and chi --ss shall be in accordance with ASIC Standard.
E Construction Method
Conductor shield, insulation and insulation shield shall be installed
on the conductor using the triple extruding, dry cure method.
F. Concentric Neutral
The concentric conductor shall be composed of a number of round
annealed bare (uncoated) copper wires helically wrapped around the
cable. The number and size of the neutral wires shall be as specified
in Table I. The length of lay shall not be less than 6 nor more than
10 times the diameter over the concentric wires.
G. Overall Jacket (if required on Proposal Form)
An extruded, encapsulating and insulating layer of linear, low density
black polyethylene, (Union Carbide DFDB 6425, British Petroleum BP D
9956 or approved equivalent) shall be applied over the concentric
s-2 11/06/92
S#CABLEX/TXTU.01D
neutral wires i n accordance with ICEA S-66-524, Part 4.3, except where
modified by this Specification. The minimum thicknesses of this
encapsulating jacket over the concentric wires shall be as follows:
Conductor Size
AAG o r KCM)
#2
#2/0
750 & 1,000
Minimum Thickness
(Mils)
50
80
110
R Testing and Guarantee
Testing of cable shall be performed according to procedures set forth
by the ICEA, AEIC and ASTM Standards. Certified copies of pass/fail
test results shall be supplied. Any cable found defective either upon
inspection, testing or installation w i I I be returned at the
manufacturer's expense.
1 _ Specific Requirements
Any conditional bids such as "subject to availability in stock" will
be rejected. Cable shall be furnished according to Table 1 below:
TABLE I
Conductor
Size
Conc. Neutral
NEMA
AVVG or
KCM
Size - AWG
Material
Insulation
Reel Code
(No. of Strands)
(Min. No. of Wires)
Phase
(Neut.)
Thick. (Mils)
Number
#2
(7)
# 14 (10)
Alum.
(Cu)
220
5832
#2/0
(19)
til4 (9)/#12 (6)
Alum.
(Cu)
220
5832
750
(61)
#12 (24)/#10 (15)
Alum.
(Cu)
220
7848
1,000
(61)
#.10 (20)
Alum.
(Cu)
220
7848
NOTE: Refer to proposal forms for specific sizes, quantities and jacketing,
requirements.
s-3 11/06/92
SKABLEX/TXTU.010
J. Reels
1. Makeup and Length:
Reels are to be shipped full to their nudam capacities.
2. Packaging:
Each cable reel shall have adequate protective covering across the
flanges. Such covering to consist of wood members from flange to
flange covering the entire circumference of the reel (lagging).
The lagging shall be nailed to the flange perimeters and shall be
further secured with at least two steel bands around the reel,
Each end of- the cable shall be firmly secured to the reel.
3. Marking:
Each reel shall be marked with a durable label securely attached
to a flange of the reel and plainly marked stating the
destination, the purchaser's order number, shipping length of
cable on reel, weight of reel (tare weight), total weight of cable
on reel, type and size of conductor, insulation type and
thickness, voltage rating and manufacturer's identification number.
K. Shipping
Cable ends shall be adequately sealed with a water seal -type material
and plastic end caps secured by tape to prevent penetration of
moisture. There shall be no water in the stranded conductor of the
cable when the reel is shipped. Reels shall be shipped upright. All
shipments shall be prepaid, F.O.B. Lodi, California.