13 GENERAL
Meter shall be single-phase; watthour with clock dial register,
self-contained socket -type having a "lexan" cover. A label nrdwd
City of Lod$" and a sequential number beginning with 31936 shall be
factory installed 'on each meter. ` Shipping boxes shall show on the
outside, the sequential number of the meters contained within.
1.4 RATING
Fam 2S, 4 terminal, 240 volt, 3 wire, Class 200, 5 dials, M 7.2,
Test Arrp 30, multiplying factor 1.
7/90