HomeMy WebLinkAboutAgenda Report - July 11, 1990 (44)T Jp COUNCIL COMMUNICATION OF WATTHOUR METERS COUNCIL MEETING DATE JULY li, 1990 NO.: cc: Electric Utility Director Assistant Electric Utility Director Electrical Engineer EQUIPMENT SPECIFICATIONS WATTHOUR METERS 13 GENERAL Meter shall be single-phase; watthour with clock dial register, self-contained socket -type having a "lexan" cover. A label nrdwd City of Lod$" and a sequential number beginning with 31936 shall be factory installed 'on each meter. ` Shipping boxes shall show on the outside, the sequential number of the meters contained within. 1.4 RATING Fam 2S, 4 terminal, 240 volt, 3 wire, Class 200, 5 dials, M 7.2, Test Arrp 30, multiplying factor 1. 7/90